Hen a gfci receptacle device is installed on a 20-ampere branch circuit (12 awg copper), what is the minimum volume allowance (in cubic inches) required for conductor fill for each conductor in the outlet box?

Respuesta :

Answer:

2.25in³

Explanation:

For a 12 awg conductor the minimum volume allowance as stated by the NEC is 2.25in³

See attached Table 314.16(B) from NEC 2011